Bring Modbus RTU meters, heat pumps, drives and controllers into a BACnet building management system — up to 500 points as native BACnet objects, over BACnet/IP or BACnet MS/TP.
Energy meters, heat pumps, frequency drives and air handling controllers often speak only Modbus, while the building management system speaks BACnet. vMBT-02 polls the Modbus devices on its RS485 channels and presents every value as a standard object of its own BACnet device — the BMS reads it, subscribes to changes and sends commands back, without a PC or middleware in between.
Each point becomes an Analog Input, Analog Value, Binary Input or Binary Value with its own name, engineering units and COV increment. Modbus data types U16, S16, U32, S32, FLOAT32 and single bits, all four byte orders, scale and offset.
BACnet/IP over Ethernet or Wi-Fi — or BACnet MS/TP master on one RS485 channel while the other channel polls Modbus. Chosen in the configuration, same hardware.
Analog and Binary Values are commandable with the standard 16-level priority array. Commands are written to the Modbus device; when the BMS releases control, the object shows the device's own value again.
The BMS can subscribe to changes (COV) instead of polling. When a Modbus device stops answering, its objects report a communication fault in Reliability and Status_Flags — visible in the BMS right away.
Edit the point list in the browser or as a CSV file in Excel and copy it from site to site. Live values and communication status for every point. Neighbouring registers are read in one request, keeping the RS485 bus light.
Secure Boot and encrypted storage on the device, HTTPS web interface and JSON API. Vectrolink Cloud gives remote access and firmware updates without VPN or port forwarding — sold as a separate subscription.
Electricity, heat and water meters are usually Modbus-only, even in BACnet buildings. vMBT-02 reads them on RS485 and hands the BMS ready BACnet objects in kWh, kW or m³ — with COV, so trend logs stay current without heavy polling.
Equipment with a Modbus interface becomes part of the BMS: temperatures and states as inputs, set-points and on/off as commandable values with priorities, so schedules and operator overrides work as with any BACnet controller.
Where the BMS runs on BACnet MS/TP, vMBT-02 joins the trunk as a master node on one RS485 channel and polls the Modbus devices on the other. No IP network needed in the plant room.
Prepare the point list once as a CSV file, adapt slave addresses and instances in Excel, and load it into the next gateway. Remote access through Vectrolink Cloud saves site visits during commissioning and service.
| BACnet | BACnet/IP (UDP 47808, configurable) or BACnet MS/TP master (9600 – 115 200 bps, MAC 0–127) · protocol revision 16 |
| BACnet objects | Analog Input, Analog Value, Binary Input, Binary Value — up to 500 points · priority array on AV/BV |
| BACnet services | Who-Is/I-Am, Who-Has/I-Have, ReadProperty, ReadPropertyMultiple, WriteProperty, SubscribeCOV, DeviceCommunicationControl |
| Modbus | RTU master · read FC01–FC04 · write FC05, FC06, FC16 · U16/S16/U32/S32/FLOAT32, bits · 4 byte orders · scale/offset |
| RS485 Channels | 2× galvanically isolated · 1 200 – 115 200 bps · parity None / Even / Odd · one channel can carry MS/TP |
| Connectivity | Wi-Fi 802.11 b/g/n 2.4 GHz · 10/100 Mbps Ethernet |
| Configuration | HTTPS Web UI · CSV import/export (Excel) · JSON API |
| Security | Secure Boot · encrypted storage · HTTPS · user accounts |
| Remote access | Web UI, API and firmware updates via Vectrolink Cloud when internet is available |
| Power Supply | 10 – 24 V DC, < 3 W |
| Protection | IP20 · Reverse-polarity protected |
| Temperature | −20 °C to +70 °C operating |
| Housing | DIN-rail (35 mm TS), 2-module width |