Translate, remap and scale Modbus registers between any two RS485 buses, or convert Modbus RTU to TCP and back — bridge them to Vectrolink Cloud.
Most industrial sites run a mix of devices from different vendors, each speaking Modbus with its own register layout, addressing scheme and scaling. vMT-02 sits between them and handles the translation — no custom PLC code, no middleware PC.
Define a mapping table: read coil 0x0001 from Device A, write it as holding register 0x0064 to Device B. Map any register type to any other — coils, discretes, input registers, holding registers.
Apply linear transform (y = ax + b) per register. A VFD that reports speed as 0–32767 → 0–50 Hz can be exposed as 0–5000 rpm to a PLC — without touching either device's firmware.
Aggregate registers from multiple slaves on RS485-1 into a single, contiguous holding-register block readable by a master on RS485-2 or via Modbus TCP. One SCADA poll fetches everything.
Converts any RS485 Modbus RTU device into a Modbus TCP server on the LAN — or connects a Modbus TCP master to devices wired on RS485. Works as a standalone converter or in parallel with the mapping engine.
RS485-1 and RS485-2 run fully independent UART settings. Bridge a 9600 8N1 legacy meter to a 19200 8E1 PLC bus without any physical converter.
No need to be on the local network or log in on-site. Vectrolink Cloud gives you secure access to the Web UI and REST API from any browser, anywhere with internet — no VPN, no port forwarding. Sold as a separate subscription to the vMT-02 device.
| Reg | Value | Meaning |
|---|---|---|
| 40001 | 18500 | Speed Hz×100 |
| 40002 | 0x04 | Status |
| 40003 | 2340 | Current mA |
| 40004 | 4800 | Voltage V×10 |
| 00001 | 1 | Run coil |
| Reg | Value | Meaning |
|---|---|---|
| 100 | 1110 | Speed rpm |
| — | — | — |
| 101 | 2.34 | Current A |
| — | — | — |
| 200 | 1 | Run mirror |
| x | Raw register value from source device |
| a | Scale factor (float32) |
| b | Offset (float32) |
| y | Value written to destination register |
| VFD Hz×100 | 18500 → 1110 rpm |
| a=0.06, b=0 | 0.06 × 18500 = 1110 |
| Temp °C×10 | 235 → 23.5 °C |
| a=0.1, b=0 | 0.1 × 235 = 23.5 |
| Pressure w/ offset | 1000 → 50 bar |
| a=0.1, b=−50 | 0.1 × 1000 − 50 = 50 |
An older Siemens VFD exposes motor speed in its proprietary register format. The site PLC expects a completely different address map. vMT-02 reads the VFD on RS485-1 and writes translated, scaled values to the PLC on RS485-2 — in real time, cycle after cycle.
Three Janitza energy meters sit on an RS485 bus, each with its own register layout starting at offset 0. vMT-02 remaps all three into a unified 0–999 / 1000–1999 / 2000–2999 address space and serves it as Modbus TCP to the SCADA system — with one polling address.
A BMS controller speaks Modbus TCP but HVAC units are RS485-only. vMT-02 bridges the protocols, optionally remapping setpoint registers to match the BMS's expected data model.
A pump station with no public IP address. vMT-02 tunnels all mapped Modbus data to Vectrolink Cloud. Operations can read live sensor values and push new setpoints from a browser — without opening any firewall port.
| RS485 Channels | 2× galvanically isolated, fully independent (RS485-1, RS485-2) |
| Baud Rate | 1 200 – 115 200 bps per channel, independently configurable |
| Parity | None / Even / Odd per channel |
| Modbus functions | FC01 FC02 FC03 FC04 |
| Mapping table | Up to 512 register-mapping rules |
| Scaling | Linear y = ax + b per rule |
| TCP gateway | Modbus TCP server on port 502, up to 4 concurrent clients |
| Connectivity | Wi-Fi 802.11 b/g/n 2.4 GHz (built-in antenna) · 10/100 Mbps Ethernet |
| Remote access | Web UI and REST API accessible via Vectrolink Cloud when internet is available |
| Power Supply | 10 – 24 V DC, < 3 W |
| Protection | IP20 · Reverse-polarity protected |
| Temperature | −20 °C to +70 °C operating |
| Housing | DIN-rail (35 mm TS), 2-module width |
| Indicators | 1× multicolor status LED (power / activity / cloud) |
| Configuration | Web UI · REST API |
| Certifications | CE |
Documentation: Client Manual (PDF) · API Reference (PDF)
Mount on DIN rail. Connect 10–24 V DC. Both RS485 buses connect to screw terminals (A / B / GND per channel).
Plug in an Ethernet cable, or use Wi-Fi: on first boot vMT-02 opens a hotspot — connect, enter your SSID and password and the device joins your LAN.
Open the web UI (IP shown on Cloud or mDNS) and add translation rules: source channel + register → destination channel + register + scale factor.
Enable the mapping engine. The status LED blinks on every translated transaction. Check the live frame counter for errors.
Vectrolink Cloud shows all mapped register values in real time. Set alert thresholds. Update the mapping table remotely without touching the device.
Tell us how many units you need — we reply with a quote and lead time. Questions about your register mapping are welcome too.