Vectrolink
Modbus Translator & RTU/TCP Converter Available now

vMT-02

Translate, remap and scale Modbus registers between any two RS485 buses, or convert Modbus RTU to TCP and back — bridge them to Vectrolink Cloud.

2× RS485
512 mapping rules
RTU↔TCP
DIN-rail
Vectrolink vMT-02

What it does

Most industrial sites run a mix of devices from different vendors, each speaking Modbus with its own register layout, addressing scheme and scaling. vMT-02 sits between them and handles the translation — no custom PLC code, no middleware PC.

⇄

Register remapping

Define a mapping table: read coil 0x0001 from Device A, write it as holding register 0x0064 to Device B. Map any register type to any other — coils, discretes, input registers, holding registers.

×

Parameter scaling

Apply linear transform (y = ax + b) per register. A VFD that reports speed as 0–32767 → 0–50 Hz can be exposed as 0–5000 rpm to a PLC — without touching either device's firmware.

↕

Address space consolidation

Aggregate registers from multiple slaves on RS485-1 into a single, contiguous holding-register block readable by a master on RS485-2 or via Modbus TCP. One SCADA poll fetches everything.

⟷

RTU ↔ TCP converter

Converts any RS485 Modbus RTU device into a Modbus TCP server on the LAN — or connects a Modbus TCP master to devices wired on RS485. Works as a standalone converter or in parallel with the mapping engine.

⇅

Baud-rate & parity bridging

RS485-1 and RS485-2 run fully independent UART settings. Bridge a 9600 8N1 legacy meter to a 19200 8E1 PLC bus without any physical converter.

☁

Manage devices from anywhere

No need to be on the local network or log in on-site. Vectrolink Cloud gives you secure access to the Web UI and REST API from any browser, anywhere with internet — no VPN, no port forwarding. Sold as a separate subscription to the vMT-02 device.

How it works — diagrams

Register remapping — how it works
DEVICE A · RS485-1
VFD – Siemens G120
RegValueMeaning
4000118500Speed Hz×100
400020x04Status
400032340Current mA
400044800Voltage V×10
000011Run coil
RS485-1
9600 8N1
vMT-02
Mapping engine
Rule 1
40001 → 100
× 0.006 (Hz→rpm)
Rule 2
40003 → 101
× 0.001 (mA→A)
Rule 3
coil 00001 → 200
1:1 mirror
RS485-2
19200 8E1
DEVICE B · RS485-2
PLC – Schneider M241
RegValueMeaning
1001110Speed rpm
———
1012.34Current A
———
2001Run mirror
Key point: Device A and Device B never "see" each other. Each talks to vMT-02 on its own RS485 segment at its own baud rate. vMT-02 polls Device A, applies the mapping rules, and writes the result to Device B — transparently, every 100 ms.
Protocol bridge modes
Mode A — RTU → TCP
Legacy RS485 device exposed on LAN as Modbus TCP server
Energy meter
RS485 RTU slave
vMT-02
SCADA
TCP :502
SCADA connects to vMT-02:502 via TCP. vMT-02 translates every TCP request into RS485 RTU, queries the meter, and returns the response in under 50 ms.
Mode B — TCP → RTU
TCP-only PLC controls RS485 devices on the field bus
PLC
Modbus TCP
vMT-02
VFD #1
VFD #2
PLC sends Modbus TCP frames. vMT-02 converts them to RTU and routes to the correct slave on RS485 — with optional address remapping.
Mode C — RS485 ↔ RS485
Two isolated RS485 segments at different baud rates
Master PLC
19200 8E1
RS485-1
vMT-02
baud convert
RS485-2
Slave A
9600 8N1
Slave B
9600 8N1
Master sends RTU at 19200 bps. vMT-02 receives on RS485-1, reframes and retransmits on RS485-2 at 9600 bps — transparent, no slave reconfiguration needed.
Mode D — All modes simultaneously
Mapping + TCP gateway + cloud tunnel run in parallel
RS485-1
RS485-2
↕
vMT-02
↕
LAN / TCP
Cloud
Real-world scenarios
Manufacturing
Legacy VFD ↔ Modern PLC
Siemens VFD
reg 40001 = Hz×100
→
vMT-02
× 0.006
→
PLC
reg 100 = rpm
No PLC code change. No VFD reconfiguration. vMT-02 polls the VFD every 100 ms, scales the value and writes to the PLC register.
Energy metering
3× meters → unified SCADA address space
Janitza #1
reg 0–49
Janitza #2
reg 0–49
Janitza #3
reg 0–49
→
vMT-02
remap:
0–49/50–99/100–149
→
SCADA
1 TCP poll
Three meters, each with slave ID 1. vMT-02 polls each individually, consolidates into a contiguous address space, and serves SCADA as one virtual slave.
Building automation
BMS ↔ HVAC units
BMS
TCP, reg 500
→
vMT-02
TCP→RTU
500→0x0032
→
HVAC #1
HVAC #2
BMS writes setpoint to reg 500 via TCP. vMT-02 converts to RS485 RTU and remaps to vendor register 0x0032 in each HVAC unit.
Remote monitoring
Off-site plant — no public IP
Pumps RS485
Flow meters
→
vMT-02
WSS tunnel
→
Cloud
→
Browser
Device behind NAT/4G with no static IP. Encrypted outbound tunnel keeps the connection alive. Operations read live data and push setpoints from a browser — no open firewall ports.
Scaling engine & mapping table
Linear scaling formula
y = a · x + b
xRaw register value from source device
aScale factor (float32)
bOffset (float32)
yValue written to destination register
Example conversions
VFD Hz×10018500 → 1110 rpm
a=0.06, b=00.06 × 18500 = 1110
Temp °C×10235 → 23.5 °C
a=0.1, b=00.1 × 235 = 23.5
Pressure w/ offset1000 → 50 bar
a=0.1, b=−500.1 × 1000 − 50 = 50
Mapping table (up to 512 rules)
Source
→ Destination
Scale (a·x+b)
Type
CH1:40001
→ CH2:100
×0.06 +0
HR→HR
CH1:40003
→ CH2:101
×0.001 +0
HR→HR
CH1:00001
→ CH2:200
×1 +0
Coil→HR
CH1:30010
→ CH2:300
×0.1 −50
IR→HR
CH2:40100
→ TCP:0
×1 +0
HR→TCP
rule 6…512
…
Register types that can be mixed:
HR = Holding register (FC03/FC06/FC16)
IR = Input register (FC04, read-only)
Coil = FC01/FC05
DI = Discrete input (FC02)
TCP = value exposed to Modbus TCP clients

Use cases

Manufacturing

Legacy VFD ↔ Modern PLC

An older Siemens VFD exposes motor speed in its proprietary register format. The site PLC expects a completely different address map. vMT-02 reads the VFD on RS485-1 and writes translated, scaled values to the PLC on RS485-2 — in real time, cycle after cycle.

Energy metering

Multi-meter aggregation

Three Janitza energy meters sit on an RS485 bus, each with its own register layout starting at offset 0. vMT-02 remaps all three into a unified 0–999 / 1000–1999 / 2000–2999 address space and serves it as Modbus TCP to the SCADA system — with one polling address.

Building automation

BMS ↔ HVAC units

A BMS controller speaks Modbus TCP but HVAC units are RS485-only. vMT-02 bridges the protocols, optionally remapping setpoint registers to match the BMS's expected data model.

Remote monitoring

Off-site plant visibility

A pump station with no public IP address. vMT-02 tunnels all mapped Modbus data to Vectrolink Cloud. Operations can read live sensor values and push new setpoints from a browser — without opening any firewall port.

Technical Specifications

RS485 Channels 2× galvanically isolated, fully independent (RS485-1, RS485-2)
Baud Rate 1 200 – 115 200 bps per channel, independently configurable
Parity None / Even / Odd per channel
Modbus functions FC01 FC02 FC03 FC04
Mapping table Up to 512 register-mapping rules
Scaling Linear y = ax + b per rule
TCP gateway Modbus TCP server on port 502, up to 4 concurrent clients
Connectivity Wi-Fi 802.11 b/g/n 2.4 GHz (built-in antenna) · 10/100 Mbps Ethernet
Remote access Web UI and REST API accessible via Vectrolink Cloud when internet is available
Power Supply 10 – 24 V DC, < 3 W
Protection IP20 · Reverse-polarity protected
Temperature −20 °C to +70 °C operating
Housing DIN-rail (35 mm TS), 2-module width
Indicators 1× multicolor status LED (power / activity / cloud)
Configuration Web UI · REST API
Certifications CE

Documentation: Client Manual (PDF) · API Reference (PDF)

Getting started

1
Wire and power

Mount on DIN rail. Connect 10–24 V DC. Both RS485 buses connect to screw terminals (A / B / GND per channel).

2
Join your network

Plug in an Ethernet cable, or use Wi-Fi: on first boot vMT-02 opens a hotspot — connect, enter your SSID and password and the device joins your LAN.

3
Build mapping table

Open the web UI (IP shown on Cloud or mDNS) and add translation rules: source channel + register → destination channel + register + scale factor.

4
Activate and verify

Enable the mapping engine. The status LED blinks on every translated transaction. Check the live frame counter for errors.

5
Monitor remotely

Vectrolink Cloud shows all mapped register values in real time. Set alert thresholds. Update the mapping table remotely without touching the device.